Ground joint unions shall be installed on pipe 2-1/2" and under where indicated on drawings. Whenever piping<br />

is connected to a major piece of apparatus, unions shall be provided as near as practical on each side of the<br />

apparatus.<br />

ISOLATION FITTINGS:<br />

Approved isolation fittings shall be installed at the junction of all copper and steel piping to prevent electrolytic<br />

action. Fittings shall be as manufactured by Walter Vallett Co., Corrosion Services, or approved equal.<br />

THERMOMETERS:<br />

General: Provide liquid-in-glass type thermometers unless bimetal dial type is required due to space limitations<br />

or other specific conditions.<br />

Scale and Dial: Provide liquid-in-glass thermometers of the organic liquid type having a nominal scale length of<br />

not less than 7 inches. Provide bimetal dial thermometers with a nominal 5-inch dial size graduated through a<br />

minimum arc of 270 degrees. Provide a recessed dial so that graduated portion and pointer are in the same<br />

plane.<br />

Range: Temperature range shall be as shown on the drawings or as specified. Chilled water system 20<br />

degrees F. to 120 degrees F.<br />

Case: Provide liquid-in-glass type thermometer with an aluminum alloy or steel case. Provide bimetal dial<br />

thermometers with all exposed metal parts, including the case and stem made of 300 Series stainless steel, all<br />

welded construction.<br />

Accuracy and Calibration: Bimetal dial thermometers shall have zero adjustment for recalibration and shall have<br />

an accuracy of plus or minus one percent of span through the complete range. Liquid-in-glass thermometers<br />

used for indicating shall have an accuracy of plus or minus 0.5 degree F. Unless otherwise required in other<br />

sections of the specifications, thermometers for commissioning tests shall have an accuracy of plus or minus<br />

0.25 degree F.<br />

Thermometers measuring temperature for energy calculations shall have an accuracy of plus or minus 0.1<br />

degree F.<br />

Thermometer Wells: Provide pipe line liquid-in-glass thermometers with a union connection, tapered bulb<br />

chamber and matching taper on well. Provide bimetal dial thermometers with a well to match bulb chamber.<br />

Provide wells for insulated pipe of the extension neck type suitable for insulation thickness. Provide wells<br />

fabricated of bronze, brass or 316 stainless steel suitable for the fluid or gas in the pipe.<br />

Stem: Provide stems with a minimum length of 2-1/2 inches immersion which shall be increased in length as<br />

necessary to reach the center lines of the pipes in which they are installed.<br />

Adjustment: Provide straight or angle pattern adjustable type thermometers as required to facilitate readings.<br />

Thermometers shall be Palmer, Trerice, Marsh or Weiss. Install all thermometers so as to be easily readable<br />

from the floor.<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-13