cocks.<br />

Backflow preventers shall be located at a maximum of 4' - 0" A.F.F. and shall be accessible for service.<br />

Backflow preventers shall have a water filter with a replaceable cartridge.<br />

GAS PRESSURE REGULATORS:<br />

Furnish and install, as required, approved type gas pressure regulators in gas piping ahead of appliance and<br />

equipment. Regulators located outside of building shall have weatherproof vent with bugproof screen.<br />

Regulators located inside of building shall be vented to the outside with approved cap screen. Approved<br />

manufacturers of gas regulators are Fisher and Reliance.<br />

PART 3.00 - EXECUTION<br />

PRODUCT HANDLING:<br />

Protection:<br />

Use all means necessary to protect plumbing materials before, during, and after installation and to protect<br />

the installed work and materials of all other trades.<br />

Replacements:<br />

In the event of damage, immediately make all repairs and replacements necessary to the approval of the<br />

Owner and at no additional cost to the Owner.<br />

TESTING:<br />

Furnish all required personnel and equipment and make all tests required to receive the approval of the<br />

Owner and all agencies having jurisdiction.<br />

CLEANING UP:<br />

Prior to acceptance of the building, thoroughly clean all exposed portions of the plumbing installation,<br />

removing all labels and all traces of foreign substance, using only a cleaning solution approved by the<br />

manufacturer of the plumbing item and being careful to avoid all damage to finished surfaces.<br />

ROOF DRAIN LOCATIONS:<br />

This contractor shall review the architectural and structural drawings and shall field verify from actual job site<br />

conditions that the roof drains are located at the low points of the roof systems. Locations shown on the<br />

plumbing drawings are approximate. All low points on the roof shall have primary and secondary roof drains<br />

installed in them unless otherwise noted.<br />

WATER CLOSET INSTALLATION:<br />

General: Install water closets as shown on the drawing and as follows:<br />

___________________________________________________________________________________<br />

____________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

PLUMBING 15400-6