a. Where available as standard products, provide pulse start metal halide<br />

ballasts for maximum energy savings.<br />

H. Three or four lamp fluorescent fixtures located within 10 feet of each other, and arranged for<br />

2 or 3 level lighting shall have master/slave ballasts wired in such a manner that a single<br />

switch shall not operate the outer lamps in some fixtures, and the inner lamps in others. One<br />

ballast shall serve outer lamps and the other shall serve inner lamp(s).<br />

L. In indoor locations other than dwellings or hazardous locations, fluorescent luminaries that<br />

utilize double-ended lamps and contain ballast(s) that can be serviced in place shall have a<br />

quick disconnecting means factory installed, internal to the luminaire, and accessable from<br />

the ballast housing. The quick disconnect shall simultaneously break all of the supply<br />

conductors to the ballast, including the neutral. The line side terminals of the disconnect shall<br />

be guarded.<br />

2.4 LAMPS:<br />

A. Provide Premium grade, high performance T8 lamps, low mercury TCLP complaint (green<br />

ends), 3100 lumens, 4100°K, CRI of 82.<br />

B. Biaxial and compact fluorescent lamps shall be 4100°K type with a minimum CRI of 82,<br />

unless otherwise noted. Provide low mercury TCLP compliant lamps (green ends) where<br />

available as standard products (Philips Alto series or equal).<br />

C. Metal Halide high intensity discharge lamps shall be either coated or clear as recommended<br />

by the fixture manufacturer. Provide pulse start lamps for Metal Halide fixtures requiring<br />

pulse start. Provide minimum CRI of 65.<br />

D. Provide Ceramic Metal Halide (Philips Master Color) with minimum CRI of 80 for display type<br />

lamps. Provide Low mercury TCLP compliant (green end) where available as standard<br />

product.<br />

E. For Metal Halide lamps, provide Base Up, or Horizontal rated lamps for maximum lumen<br />

output. Universal Burn lamps are not acceptable.<br />

F. All incandescent lamps shall be 130 volt, inside frosted unless otherwise noted (except<br />

Halogen).<br />

G. Acceptable lamp manufacturers are Venture, Osram/Sylvania, Philips, and General Electric.<br />

H. All lamps and fixtures shall be in proper operation at the time of acceptance.<br />

I. SPARE LAMPS: Provide ten percent spare lamps, with a minimum of two, for each size and<br />

type used.<br />

2.5 POLES:<br />

A. Each pole shall have adequate strength and rigidity to withstand not less than 100 mph winds<br />

without damage to the poles and attached fixtures and lamps. Pole bases shall be equipped<br />

with handholes with matching covers, and base cover.<br />

B. Anchor bolts shall be hot-dip galvanized after fabrication and threads cleared. Nuts,<br />

washers, and other hardware and fittings shall be corrosion resistant alloy material of<br />

adequate strength. Indicated pole heights are above the top of the concrete base.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

LIGHTING Section 16500-4