PRESSURE GAUGES:<br />

General: Provide pressure gauges which comply with ANSI B40.1.<br />

Dials: Provide dials not less than 4-1/2 inches in diameter, except that packaged equipment may be provided<br />

with manufacturer's standard gauges of equal accuracy.<br />

Ranges: Select operating ranges so that during normal service the gauge pointer will be at the approximate<br />

midpoint of the gauge scale.<br />

Refrigerant Gauges: Provide refrigerant pressure gauges with corresponding temperature scales for the<br />

particular refrigerant sensed.<br />

Accuracy: Pressure gauges used for commissioning of other equipment shall have a minimum accuracy of 3<br />

percent of span.<br />

Gauge Cocks: All gauges shall be furnished with gauge cocks and pressure snubbers.<br />

Gauges shall be Ashcroft, Trerice, or U.S. Gage.<br />

PRESSURE & TEMPERATURE TEST PLUGS:<br />

Plugs shall be brass body type with Neoprene, Nordel, or Vitron self-closing valve (to suit temperatures of fluid in<br />

pipe). Test plugs shall be Pete's Plug or approved substitute. Furnish six pressure and six temperature<br />

instruments to Owner to permit reading pressures and temperatures.<br />

FLOW MEASURING AND BALANCING SYSTEMS:<br />

Furnish and install complete the Venturi and calibrated orifice Flow Metering Systems as shown on the<br />

drawings.<br />

This shall be a coordinated system with individual Venturi Flow Stations supplied by one manufacturer and each<br />

individual calibrated orifice supplied by one manufacturer.<br />

On pipe sizes 3/4-inch diameter and smaller, provide calibrated balancing valves on runouts to fan coil units, fin<br />

tube radiation, convectors and reheat coils.<br />

Fittings shall be of the combination balancing and shut-off type with the balancing device positioned by an Allen<br />

set screw or other approved method which permits closing of the valves without disturbing its balanced position.<br />

Bodies may be of the globe or "Y" type with contour flow plug or approved equivalent.<br />

Provide a graduated dial or other device to indicate the valve setting.<br />

Gland shall permit packing under pressure.<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-14