Size Cv<br />

4 209<br />

5 315<br />

6 462<br />

7 612<br />

8 817<br />

10 1250<br />

12 1792<br />

14 2474<br />

16 3235<br />

PACKAGED AIR CONDITIONER (AC-1):<br />

Furnish and install complete the air-to-air split system packaged air conditioner shown and specified on the<br />

drawings.<br />

Evaporator section shall be ceiling mounted type with pre-charged refrigerant system, packaged controls,<br />

swing flow outlet air louvers, and packaged, integral, concealed drain pump. Unit shall be complete with<br />

filter section, hard wired, wall mounted thermostat, and all controls for automatic operation.<br />

Condensing unit section shall be complete with high performance hermetic compressor with high and low<br />

pressure safety controls, air cooled condenser with modulating fan controls for operation at outdoor air<br />

temperatures as cold as 0N F.<br />

Unit shall be EMI, Carrier, Mitsubishi or approved equal.<br />

AIR FILTERS:<br />

Provide one complete set of spare filter media (in addition to the new filters installed at time of acceptance)<br />

for each unit filter bank and store on site as directed by Architect.<br />

Air filter banks shall be Cambridge, AAF, or Eco-Air.<br />

HVAC SMOKE DETECTORS:<br />

All units above 2000 CFM shall be provided with smoke detectors located in the return air intake and supply<br />

air discharge as per IMC. Detectors to be provided and wired under Section 16000. Mechanical contractor<br />

shall install all detectors, and ATC contractor shall wire fan shutdown. See specification section 15900.<br />

Duct smoke detectors shall not be installed until just prior to final inspection to prevent dust and debris from<br />

contaminating detector.<br />

COMBINATION FIRE AND SMOKE DAMPERS:<br />

-<br />

___________________________________________________________________________________<br />

____________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

AIR DISTRIBUTION 15800 - 11