Insulation on all cold surfaces where vapor barrier jackets are used will be applied with a continuous, unbroken<br />

vapor seal. Hangers, supports, anchors, etc., that are secured directly to cold surfaces must be adequately<br />

insulated and vapor-sealed to prevent condensation.<br />

Valves and fittings inside the building shall be insulated as specified for the piping systems and covered with<br />

high temperature P.V.C. insulation fitting covers.<br />

Fittings and valves for pipe size smaller than 4" shall be insulated and finished with Insulating and Finishing<br />

Cement to a thickness equal to the adjoining pipe insulation. Fittings and valves for pipe sizes 4" and larger shall<br />

be insulated with segments of the molded insulation secured with No. 20 gage galvanized annealed steel wire<br />

finished with a smoothing coat of finishing cement. Vapor seal with a layer of glass fabric embedded between<br />

two 1/16" coats of vapor seal adhesive. Lap seal outer jacket at least 1" on itself adjoining insulation.<br />

In exposed areas, all fittings shall be additionally finished with FSK wrap smoothly adhered. Overlap the FSK<br />

wrap on itself and adjoining pipe insulation. Overlap to be at least 1" on pipe insulation below 4" and 2" on sizes<br />

4" and above. Piping exposed in occupied areas shall have a white PVC cover installed.<br />

Insulation inserts and shields for cold surface piping such as roof drain lines and domestic cold water piping shall<br />

be installed at all pipe hangers. Inserts between the pipe and pipe hangers shall consist of calcium silicate block<br />

insulation of equal thickness to the adjoining insulation and shall be provided with vapor barrier where required.<br />

Insulation inserts shall not be less than the following lengths, unless otherwise approved on submittals:<br />

1/2" to 2-1/2" pipe size 6" long<br />

3" to 6" pipe size 9" long<br />

8" to 10" pipe size 12" long<br />

Rigid metal shields shall be applied between hangers or supports and the pipe insulation. Shields shall be<br />

formed to fit the insulation and shall extend up to the centerline of the pipe and length specified for the insulation<br />

hanger inserts.<br />

Vapor barrier wrap shall be sealed tight and not penetrated by the hanger or shield.<br />

Block insulation shall be applied with edges tightly butted, joints broken, and secured with No. 16 gauge<br />

galvanized annealed steel wire or 1/2" x .015" galvanized steel bands on 12" maximum centers for large areas.<br />

Where required, welded studs, clips, or angles shall be provided as anchored for fire and bands. Finish shall be<br />

Insulating and Finishing Cement applied 1/4" thick in one coat, trowelled to a smooth finish. Over the Insulating<br />

and Finishing Cement an FSK outer jacket cloth shall be smoothly adhered with vapor barrier adhesive.<br />

Insulation blocks shall be applied with edges tightly butted, joints broken, and secured with No. 14 gauge<br />

galvanized annealed steel wire, or 1/2" X 0.15" galvanized steel bands on 12" maximum centers for large areas.<br />

Where required, welded studs, clips, or angles shall be provided as anchored for wires and bands.<br />

Over the insulation, 1" hexagonal mesh wire shall be tightly stretched in place and secured by wiring to anchors,<br />

with edges tied together. Finish shall be Johns-Manville No. 3011 Insulating and Finishing Cement or approved<br />

equal applied 1/4" thick in one coat, trowelled to a smooth finish.<br />

Over the Insulating and Finishing Cement, pre-sized glass cloth shall be smoothly adhered with Adhesive.<br />

__________________________________________________________________________________________________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

INSULATION 15180-4