e. EXHAUST FANS START-STOP<br />

f. 120 F CULINARY SYSTEM ENABLE-DISABLE<br />

g. VAV BOXES ALL DATA<br />

2. DIGITAL INPUTS:<br />

a. CHILLER (each compressor) RUN STATUS<br />

b. CHILLER STATUS<br />

c. CHILLER FAILURE ALARM (1) SAFETY SHUTDOWN<br />

d. CHILLED WATER FLOW (1) STATUS<br />

e. SUPPLY FAN VFD STATUS<br />

f. BUILDING FIRE ALARM SYSTEM STATUS<br />

g. FREEZE PROTECTION THERMOSTAT STATUS<br />

h. DISCHARGE DUCT HIGH STATIC STATUS<br />

i. 0-6 HOUR OVERRIDE TIMER STATUS<br />

j. HEATING WATER PUMPS STATUS<br />

k. CHILLED WATER PUMP STATUS<br />

l. CHILLED WATER FLOW STATUS<br />

m. VAV BOXES ALL DATA<br />

3. ANALOG INPUTS:<br />

a. CHILLED WATER SUPPLY TEMP<br />

b. CH1LLED WATER RETURN TEMP<br />

c. HOT WATER SUPPLY TEMP<br />

d. HOT WATER RETURN TEMP<br />

e. CULINARY 120 F STORAGE TANK TEMP<br />

f. BOILER TEMP<br />

g. OUTDOOR – AIR TEMP TEMP<br />

h. RETURN AIR CARBON DIOXIDE SENSOR CO2<br />

i. SUPPLY AIR TEMP TEMP<br />

j. MIXED AIR TEMP TEMP<br />

k. RETURN AIR TEMP TEMP<br />

l. VAV SYSTEM SUPPLY DUCT STATIC PRESS<br />

m. FILTER BANK PRESS<br />

n. VAV BOXES ALL DATA<br />

4. ANALOG OUTPUTS:<br />

a. FAN SYSTEM HEATING VALVE Mod<br />

b. SYSTEM COOLING VALVE Mod<br />

c. SYSTEM OA AND RA DAMPERS Mod<br />

d. BUILDING RELIEF DAMPERS Mod<br />

e. SUPPLY FAN VFD Mod<br />

f. VAV BOXES ALL DATA<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-17