secondary water differential temperature and water flow to the building.<br />

E. The chilled water supply temperature shall be reset based on outside air temperature<br />

according to the following schedule:<br />

Outside Air Temperature CHS Temperature<br />

95 0 F 45 0 F<br />

55 0 F 50 0 F<br />

F. Interface the BMCS with the chiller interface panel. Provide on-off control and monitoring,<br />

CHS supply temperature control and monitoring, demand limiting and general alarm<br />

monitoring.<br />

4.7 VAV SUPPLY AIR FAN SYSTEMS<br />

A. The air handler shall be equipped with supply fan; hot water preheat and chilled water<br />

coils; angle filter bank; outside air and return air dampers.<br />

B. Systems shall be individually started, stopped and controlled by the building energy<br />

management system (BAS). Provide manual 0-6 hour override timers (2) located as<br />

directed to provide local override of each fan system to the OCCUPIED mode.<br />

C. Supply fan speeds are controlled by VFD's.<br />

D. 0-2" w.c. supply duct static pressure transmitters located where shown on the plans and<br />

acting through DDC controllers shall modulate each VFD to maintain required supply duct<br />

static pressure. Duct static pressure shall be reset from zone requiring most cooling. Duct<br />

static pressure transmitters shall have an accuracy of 2% or better.<br />

E. A manual reset high limit pressure switch sensing discharge duct static shall shut down<br />

the fan if its setting is exceeded.<br />

F. Minimum Outside Air Control - The minimum outside air flow shall be controlled between<br />

the upper and lower air flows by a CO2 sensor, If the CO2 level is below setpoint (800<br />

PPM), the outside air dampers shall close to the lower air flow. The outside air dampers<br />

and return air dampers will modulate to maintain the minimum air flow.<br />

G. During the OCCUPIED mode and when the outdoor air temperature is below 55 F, a<br />

DDC controller shall modulate the boiler water temperature and the outdoor air and<br />

return air dampers in sequence to maintain discharge air temperature according to the<br />

following schedule:<br />

Outdoor Air Temperature Discharge Air Temperature<br />

55 F 55 F<br />

0 F 60 F<br />

H. If the outside air temperature is above 72 F, the outside air damper shall close to the<br />

minimum CFM position and the return air damper shall open correspondingly.<br />

I. The amount of outdoor air passing through the outdoor air damper and the outdoor air<br />

damper position shall be measured and displayed at the boiler room ATC panel.<br />

J. A return air temperature sensor shall prevent the outdoor air damper from opening until<br />

the return air temperature rises above 68 deg, F.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-14