through 12-inch diameter shall meet the requirements of AWWA C 900 with pressure class of 150<br />

and DR of not less than 18. PVC pipe of 14-inch through 36-inch diameter shall meet the<br />

requirements of AWWA C-905 with pressure rating of not less than DR 18. Each length of pipe<br />

shall be capable of withstanding without failure 600 psi hydrostatic pressure for a minimum of<br />

5 seconds. The integral bell shall be tested with the pipe.<br />

B. Provisions shall be made for contraction and expansion at each joint with a rubber ring and<br />

integral thickened bell as part of each joint. The rubber ring shall meet the requirements of<br />

ASTM D 1869. The bell section shall be at least as strong as the pipe barrel.<br />

1. At least 85 percent of the total footage of pipe shall be furnished in standard lengths of<br />

20 feet. The remaining footage of pipe may be in random lengths of not less than 10 feet<br />

long.<br />

Sizes and their respective dimensions shall be as specified in the following tabulation:<br />

Nominal Pipe<br />

Size (Inches)<br />

4<br />

6<br />

8<br />

10<br />

12<br />

Outside Pipe<br />

Diameter<br />

(Inches)<br />

4.80<br />

6.90<br />

9.05<br />

11.10<br />

13.20<br />

PART 38 FITTINGS FOR PVC PIPE<br />

Minimum Pipe<br />

Wall<br />

Thickness (Inches)<br />

0.282<br />

0.406<br />

0.532<br />

0.653<br />

0.776<br />

A. Fittings for PVC pipe shall be cast iron fittings as specified under cast iron and ductile iron pipe in<br />

these <strong>Specification</strong>s and properly sized for the dimensions of the pipe being used. All fittings for<br />

joining pipe 4 inches in diameter and larger shall be of the push-on rubber gasket or mechanical<br />

joint type of joint.<br />

PART 39 PVC PIPE LEAKAGE TEST<br />

A. All PVC pipe shall be tested for leakage at 150 psi per AWWA C 605-97, measured at the lowest<br />

point in the line. Any sections of pipelines indicating more than the allowable leakage shall be<br />

repaired and retested until the leakage is less than the allowable indicated below. The leakage test<br />

shall be for a minimum duration of 2 hours. The leakage test shall be made after backfilling. Any<br />

visible leaks shall also be repaired.<br />

Pipe Diameter<br />

Inches<br />

4<br />

6<br />

8<br />

10<br />

12<br />

14<br />

16<br />

18<br />

20<br />

24<br />

Allowable Leakage<br />

Gallons/100 Joints/Hour<br />

0.33<br />

0.50<br />

0.66<br />

0.83<br />

0.99<br />

1.16<br />

1.32<br />

1.49<br />

1.66<br />

1.99<br />

PART 40 RUBBER HOSE<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION 02630 - 15<br />

PIPING, VALVE, GATES AND SPECIALTIES MARCH 2, 2009