air flow. The discharge air temperature shall be limited to 100<br />

Deg F.<br />

4) The BAS shall limit the maximum cooling setpoints to 75 Deg F.<br />

(adjustable) and the minimum cooling setpoint to 73 Deg F.<br />

(adjustable).<br />

5) The BAS shall limit the maximum heating setpoint to 72 Deg F.<br />

(adjustable) and the minimum heating setpoint to 70 Deg F.<br />

(adjustable).<br />

6) If the room temperature rises 3 Deg F. (adjustable) above the<br />

cooling setpoint, the BAS shall generate an alarm. If the room<br />

temperature drops 3 Deg F. (adjustable) below the heating<br />

setpoint, the BAS shall generate an alarm.<br />

7) Convector shall be controlled in sequence with the reheat coil.<br />

Convector valve shall open first, followed by the reheat coil<br />

valve.<br />

g. Warm-up Cool-Down Mode<br />

1) When the central air handling unit is in the Warm-Up mode, the<br />

BAS shall reverse the action of the VAV box so as the room<br />

temperature drops below setpoint the box will modulate towards<br />

maximum position and as the room temperature rises above the<br />

setpoint the box will modulate towards minimum position. When<br />

the Warmup mode is concluded the VAV box shall operate in the<br />

same manner as during the Occupied Mode.<br />

2) The BAS shall command the hot water reheat valve closed.<br />

3) When the central air handling units is in the Cool-Down mode,<br />

the VAV box shall operate in the same manner as during the<br />

Occupied Mode except the heating shall be disabled.<br />

h. Energy Consumption<br />

1) The BAS shall monitor the supply air temperature to the VAV<br />

Box, the VAV room temperature and the supply air flow in CFM.<br />

2) The BAS shall monitor and totalize the energy consumption of<br />

the VAV zone in Btuh.<br />

i. VAV Room Sensor<br />

1) The VAV Room Sensor shall provide room temperature value to<br />

the controller.<br />

2) The VAV Room Sensor shall be supplied in the following<br />

manner:<br />

a) Tamper-resistant with tenant override to allow timed<br />

override of unoccupied to occupied mode of operation.<br />

b) LED indication of override state.<br />

j. Point List<br />

1) Inputs<br />

a) Al Room Temperature<br />

b) Al VAV Box Velocity Pressure<br />

c) Al VAV Box Supply Flow (CFM)<br />

d) Al Energy Consumption in BTU<br />

e) Al Totalized Energy Consumption in BTUH.<br />

f) Al VAV Supply Air Temperature.<br />

2) Outputs<br />

a) AO VAV Supply Damper<br />

b) AO Hot Water Reheat Valve<br />

c) DO Occupied Mode<br />

d) AO Convector Valve<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION<br />

AUTOMATIC TEMPERATURE CONTROLS 15900-12