B. COMBINATION STARTER/DISCONNECTS – STAND ALONE UNITS: Subject to compliance<br />

with requirements, provide products manufacturered by one of the following:<br />

Square D<br />

GE<br />

Siemens<br />

Cutler Hammer<br />

2.2 COMBINATION STARTERS<br />

A. Starters: combination type with fused disconnect switch with time delay dual element, 3 pole,<br />

UL Class RK-5 fuses as scheduled; full voltage, non-reversing magnetic starter unless<br />

otherwise shown or noted. Provide quick make, quick break disconnect. Starters shall have<br />

electronic resettable thermal overload elements for all three phases with settings sized for the<br />

actual final motor nameplate full load current. Minimum starter size shall be NEMA 1. For<br />

sizes 4 and above, provide electronic soft start system starter.<br />

B. Each starter shall include:<br />

a. Hand-Off-Automatic selector switch unless otherwise shown or noted. HOA<br />

switch to be of a type that is field convertible to "On/Off" or "Auto/Off".<br />

b. A thermal element reset button.<br />

c. A red transformer type pilot light to indicate when the motor is running.<br />

d. A 120V holding coil.<br />

e. A 480/120V control transformer with primary and secondary fuse protection;<br />

of sufficient VA to handle the holding coil and associated controls. One leg<br />

of the transformer secondary shall be grounded.<br />

f. Two normally open and two normally closed auxiliary contacts.<br />

g. A nameplate engraved with motor identification and Horsepower, Nameplate,<br />

HOA switch, reset button and pilot light shall be mounted in cubicle door. A<br />

door mounted keypad display with indicators, allowing user to program<br />

C. Each electronic solid state starter shall include the items indicated above, plus the following<br />

items:<br />

a. Ramp time, type of start, type of step. Display to show motor current, power<br />

factor, and fault status.<br />

b. Phase loss protection and phase reversal protection.<br />

1. The solid state starter shall utilize an 18 pulse converter design, to maintain minimal<br />

AC line distortion and low harmonics.<br />

2. The Solid State Starter and all components shall be rated to 100,000 AIC.<br />

4. The starter shall have an adjustable ramp start of 0.5 to 180 seconds, and an<br />

adjustable current limit of 0% to 85% of Locked Rotor Current. The starter shall also<br />

have an adjustable Soft Stop from 0 to 60 seconds.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

MOTOR CONTROLLERS Section 16475-2