eams. These conditions are to be anticipated and sleeves installed as provided for under "Sleeves".<br />

INSERTS:<br />

Furnish and set, in all necessary locations, before or during construction, unistrut inserts for use in connection<br />

with the support and seismic restraint of piping, ductwork, and equipment furnished under this division of the<br />

work.<br />

SLEEVES:<br />

Sleeves for Concrete or Masonry Surfaces:<br />

For pipes passing thru masonry or concrete construction, provide sleeves at least two pipe sizes larger than the<br />

pipe passing thru and made from sections of steel pipe.<br />

Provide galvanized iron sleeves with collar on each side of wall for all ducts passing thru masonry or concrete<br />

construction.<br />

Sleeves shall be placed in structural members only where approved by the Owner's representative.<br />

Sleeves through foundation walls below grade shall be mechanical seal type with watertight sealing grommets<br />

and pressure rings. Sealing grommets shall be non-melting at temperatures incurred. Foundation wall sleeves<br />

shall be "O.Z. Type WSK".<br />

Sleeves thru Finished Surfaces:<br />

For pipes passing thru finished partitions or ceilings, provide galvanized sheet iron sleeves of suitable size. The<br />

sleeves shall be fastened to construction to prevent creep along pipe and the sleeve ends shall be flush with<br />

finished surfaces. Provide escutcheon plates at each side of finish wall or floor or ceiling for all pipes passing<br />

thru same.<br />

Sleeves thru Fire-rated Surfaces:<br />

All pipe and duct sleeves in fire walls and surfaces shall be packed inside after pipes and ducts have been<br />

placed with an approved UL listed fire insulation similar to 3M fire protection products. This contractor shall<br />

submit complete installation details for the through-penetration fire protection sleeves proposed for use on this<br />

project.<br />

Sleeves thru Sound Rated Surfaces:<br />

Sleeves thru sound rated walls or surfaces shall be installed so as to provide the same sound transfer coefficient<br />

as the surface in which they are installed. This contractor shall submit complete installation details for all sound<br />

rated sleeves.<br />

Sleeves thru Floors:<br />

Sleeves for all pipe and duct penetrations thru floors above grade shall extend 1" above the floor and shall be<br />

______________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDTION March 2, 2009<br />

BASIC MATERIALS & METHODS 15050-2