SECTION 07210 - BUILDING INSULATION<br />

PART 1 - GENERAL<br />

1.01 SUMMARY<br />

A. Section includes thermal and fire safing insulation shown on the drawings and specified<br />

herein.<br />

B. Contractor to ensure that all exterior soffits, walls and fascias enclosing interior spaces<br />

receive the appropriate type of insulation.<br />

C. Related Sections:<br />

1. Division 4 Section “Unit Masonry” for insulation placed in masonry cells.<br />

2. Division 7 Section “Manufactured Roof Panels.”<br />

3. Division 7 Section “Polyvinyl-Chloride (PVC) Roofing” for insulation below roof<br />

membrane.<br />

4. Division 9 Section “Gypsum Board Assemblies” for sound attenuation batts in gypsum<br />

board/metal stud walls.<br />

1.02 COORDINATION<br />

A. Coordinate work and scheduling of the work of this section with other trades.<br />

1.03 DELIVERY AND STORAGE<br />

A. Do not allow insulation materials to become wet or soiled, or covered with ice or snow.<br />

Comply with manufacturer's recommendations for handling, storage and protection during<br />

installation.<br />

B. Protect plastic insulation from exposure to sunlight per manufacturer's recommendations.<br />

C. Remove any damaged materials from site and replace at no additional cost to the Owner.<br />

D. Fire hazard: Do not deliver plastic insulating materials to the project site ahead of time of<br />

installation. Protect at all times against ignition. <strong>Complete</strong> the installation and concealment of<br />

placement materials as rapidly as possible in each area of work.<br />

1.04 STANDARDS<br />

A. Thermal conductivity: Thickness required is for the thermal conductivity (k-value at 75 degrees<br />

F.) specified for each material. Provide adjusted thickness, as directed, for the use of material<br />

having a different thermal conductivity.<br />

B. Fire and insurance rating: Comply with the fire resistance and flammability ratings indicated,<br />

and comply with requirements of Fire Marshal having jurisdiction.<br />

PART 2 - PRODUCTS<br />

2.01 BLANKET-TYPE BUILDING INSULATION<br />

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering<br />

products that may be incorporated in the Work include, but are not limited to the following:<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

BUILDING INSULATION 07210-1