25 year successful track record.<br />

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering<br />

products that may be incorporated into the work include the following:<br />

a. FiberTite, a Seaman Corporation.<br />

b. Sarnafil Inc.<br />

2. Thickness: 60 mils, nominal, with minimum 20 mils above reinforcing.<br />

3. Exposed Face Color: White.<br />

B. Alternate: 80 mils, nominal, with minimum 20 mils above reinforcing and a 30 year warranty.<br />

2.2 AUXILIARY MEMBRANE ROOFING MATERIALS<br />

A. General: Auxiliary membrane roofing materials recommended by roofing system manufacturer for<br />

intended use, and compatible with membrane roofing.<br />

1. Liquid-type auxiliary materials shall comply with VOC limits of authorities having jurisdiction.<br />

B. Sheet Flashing: Manufacturer's standard sheet flashing of same material, type, reinforcement,<br />

thickness, and color as PVC sheet membrane.<br />

C. Bonding Adhesive: Manufacturer's standard.<br />

D. Metal Termination Bars: Manufacturer's standard, predrilled stainless-steel or aluminum bars,<br />

approximately 1 by 1/8 inch thick; with anchors.<br />

E. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosionresistance<br />

provisions in FM Approvals 4470, designed for fastening membrane to substrate, and<br />

acceptable to membrane roofing system manufacturer.<br />

F. Coated Flashings: Manufacturer’s standard PVC coated metal flashings in thickness as<br />

recommended by manufacturer for indicated use and complying with performance requirements, but<br />

with metal thickness not less than 0.028 inches.<br />

G. Miscellaneous Accessories: Provide pourable sealers, preformed cone and vent sheet flashings,<br />

preformed inside and outside corner sheet flashings, T-joint covers, lap sealants, termination<br />

reglets, and other accessories.<br />

2.3 INSULATION MATERIALS<br />

A. Substrate Board: Rigid polyisocyanurate with black mat facers 4’ x 8’ installed in two layers to meet<br />

desired r-value.<br />

1. R-Value: 30.<br />

B. Molded-Polystyrene Board Insulation: Where tapered insulation, crickets, saddles, tapered edge<br />

strips, or other insulation shapes are indicated provide rigid, cellular polystyrene thermal insulation<br />

formed by expansion of polystyrene-resin beads or granules in a closed mold to comply with ASTM<br />

C 578 for type and with other requirements indicated below:<br />

1. Type II, 1.35-lb/cu. ft. (22-kg/cu. m) minimum density<br />

2. Where molded-polystyrene tapered insulation, crickets, saddles, tapered edge strips, or other<br />

insulation shapes are indicated, the molded-polystyrene board shall be placed between the<br />

layers of polyisocyanurate insulation.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

POLYVINYL-CHLORIDE (PVC) ROOFING 07542 - 4