3.11 ADJUSTING AND CLEANING<br />

A. Flushing: Flush underground mains and lead-in connections to sprinkler risers before<br />

connection is made to sprinklers, standpipes, or other fire protection system piping.<br />

1. Flush at flow rate not less than that indicated in NFPA 24, or at hydraulically calculated<br />

water demand rate of the system, whichever is greater.<br />

B. Adjusting: adjust fire hydrants to face street and be have base 2-6 inches above adjacent curb<br />

and gutter.<br />

3.12 CLOSING ABANDONED WATER SYSTEMS<br />

A. Abandoned Piping: Close open ends of abandoned underground piping indicated to remain in<br />

place. Include closures strong enough to withstand hydrostatic and earth pressures that may<br />

result after ends of abandoned piping have been closed. Use either procedure below:<br />

1. Close open ends of piping with at least 8-inch-thick, brick masonry bulkheads.<br />

2. Close open ends of piping with threaded metal caps, plastic plugs, or other acceptable<br />

methods suitable for size and type of material being closed. Do not use wood plugs.<br />

B. Backfill to grade according to Division 31 Section "Earth Moving."<br />

END OF SECTION 02008<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

WATER UTILITY PIPING 02008 - 8