PART 3 - EXECUTION<br />

3.1 SPLICES AND TERMINATIONS:<br />

Neutral White<br />

Equipment Ground Green<br />

Isolated Ground Green w/yellow stripe #12 & #10<br />

Green and Yellow bands #8 and up<br />

A. Splices are to be made up complete promptly after wire installation. Single wire pigtails shall<br />

be provided for fixture and device connections. Wirenuts may be used for fixture wire<br />

connections to single wire circuit conductor pigtails.<br />

B. Splices shall utilize Scotch "Hyflex" or "Ideal" wing nut connector installed properly. Splices<br />

for No. 8 and larger wires shall be made with mechanically applied pressure type connectors.<br />

All taped joints shall be with "Scotch 33+" or equal, applied in half-lap layers without<br />

stretching to deform.<br />

C. Insulation shall be removed with a stripping tool designed specifically for that purpose. A<br />

pocket knife is not an acceptable tool. All conductors shall be left nick-free.<br />

D. Thermoplastic insulated wire and cable shall not be installed or handled in temperatures<br />

below +14 degrees F (-10 C). Cross-linked polyethylene insulated wire and cable may be<br />

installed to -40 degrees F (-40 C).<br />

3.2 INSTALLATION:<br />

A. Provide dedicated neutral for each branch circuit. Use of the shared neutral for multiwire<br />

branch circuit is not allowed.<br />

END OF SECTION<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

WIRES & CABLES Section 16120-2