H. Transformer / latching relay design.<br />

I. Works with electronic ballast and high power factor PL lamp ballasts.<br />

J. No leakage current in off mode.<br />

K. Voltage drop protection.<br />

L. Watt Stopper Model WS 120 / 277<br />

2.3 CEILING MOUNT INFRARED TYPE (For offices up to 300 square feet)<br />

A. Shall utilize custom ASIC specifically designed for PIR occupancy sensors which provides<br />

high immunity to RFI and EMI.<br />

B. Shall have user-adjustable sensitivity setting and adjustable time delay of 30 seconds to 30<br />

minutes.<br />

C. Shall have in place a by-pass pin which when removed will override sensor to ON and which<br />

requires no rewiring or modification to unit.<br />

D. Shall have a daylight filter which insures that the sensor in insensitive to short-wavelength<br />

infrared waves such as those emitted by the sun.<br />

E. Shall have the ability to sense directly under and slightly behind sensor when mounted on<br />

ceiling.<br />

F. Shall not protrude more than 1 1/4 inches from the ceiling (or wall).<br />

G. Adjustments and mounting hardware shall be concealed under a removable cover to prevent<br />

tampering of adjustments and hardware.<br />

H. Shall operate from a 24 volts DC power supply: current draw of 14 milliamps.<br />

I. Watt Stopper Model WPIR<br />

2.4 CEILING MOUNT INFRARED TYPE (For Offices, Conferences Rooms up to 900 square feet).<br />

A. Shall use custom ASIC specifically designed for PIR occupancy sensors which provides high<br />

immunity to RFI and EMI.<br />

B. Shall have two outputs; one output is based on occupancy only and one is based on<br />

occupancy with a hold OFF and an internal photocell setting when a minimum light level is<br />

present (adjustable from 3 to 200 footcandles).<br />

C. Shall have a digital time delay setting adjustable from 15 seconds to 30 minutes.<br />

D. Shall be furnished with a DIP switch overrode-ON function for use in the event of failure.<br />

E. Shall have an additional single pole, double throw isolated relay with normally open, normally<br />

closed, and common outputs rated at 1 Amp for 24 VDC. The isolated relay is for use with<br />

HVAC control, data logging, and other control options.<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION March 2, 2009<br />

OCCUPANCY SENSED LIGHTING CONTROL 16550-2