2.02 MATERIALS<br />

a. Rout and return the Alucobond ! on all perimeters. “Continuous Edge Grip”<br />

(CEG) is not acceptable.<br />

b. Exposed edge of the Alucobond ! shall be protected inside an extruded<br />

aluminum pocket.<br />

c. Maximum overall panel thickness, including the attachment shim space, shall<br />

not exceed 2”.<br />

d. The Alucobond ! shall be mechanically attached to all perimeter extrusions.<br />

The mechanical fastener must not penetrate any portion of the outer (exterior)<br />

skin of the aluminum composite material. Attachment of the Alucobond ! to the<br />

perimeter extrusions with structural silicone is not allowed.<br />

e. Do not substitute sealants for dry gasketing shown at the metal panel joinery.<br />

2. Stiffeners: Extruded aluminum sections secured to edge trim and bonded to rear face<br />

of Alucobond ! with silicone, and of sufficient size and strength to maintain flatness of<br />

the panel within the specified tolerances.<br />

3. Reveals at Panel: Joint size between the faces of the perimeter extrusions shall be<br />

1/2", nominal.<br />

4. Flatness Criteria: Maximum 1/8" in 15'-0" on panel in any direction for assembled<br />

units. (Non-accumulative).<br />

A. Alucobond ! Composite Material (ACM or MCM):<br />

1. Composite: Two sheets of aluminum sandwiching a core of extruded thermoplastic,<br />

formed in a continuous process with no glues or adhesives between dissimilar<br />

materials. Total composite thickness is 4mm.<br />

2. Face Sheets: 0.020" thick .<br />

3. Color and Coating: To be selected by the architect from the Series A and/or Series B<br />

Alucobond ! color chart with the appropriate recommended coating, (2 coat or 3 coat).<br />

4. Finish: The selected coating must meet the weathering performance criteria of AAMA<br />

2605. Exterior surfaces shall be coil coated Kynar 500 ! or Hylar 5000 ! based<br />

polyvinylidence fluoride (PVDF) resin. Other resin-based coatings are not acceptable.<br />

In particular, the coating must have successfully passed the following tests:<br />

a. Humidity Resistance<br />

(1) Test Method: ASTM D-2247<br />

(a) No formation of blisters when subjected to condensing water<br />

fog at 100% relative humidity and 100 degrees Fahrenheit for<br />

4,000 hours.<br />

b. Salt Spray Resistance<br />

(1) Test Method: ASTM B-117; expose coating system to 4,000 hours,<br />

using 5% NaCl solution.<br />

(a) Minimum rating of 7 on scribe or cut edges.<br />

(b) Minimum blister rating of 8 within the test specimen field.<br />

c. Weather Exposure<br />

(1) Outdoor<br />

(a) Ten (10) year exposure at 45 degree angle facing south<br />

Florida exposure.<br />

(b) Maximum color change of 5 Delta E units as calculated in<br />

accordance with ASTM D-2244.<br />

(c) Maximum chalk rating of 8 inches accordance with ASTM D-<br />

659.<br />

(d) No checking, crazing, adhesion loss.<br />

5. Core: Thermoplastics<br />

________________________________________________________________________________________<br />

SEGO LILY ELEMENTARY SCHOOL CLASSROOM ADDITION MARCH 2, 2009<br />

COMPOSITE PANELS 07430 - 5