If the alarm is MAJOR:<br />

● Check connections between the Stratum-3 clock and the switch.<br />

STRAT-3 (Stratum-3 Clock)<br />

● If there are no loose connections, use the Stratum-3 Wiring Guide and check that the<br />

wiring installation is correct.<br />

● After reconnecting the loose connection or correctly rewiring it, clear the alarm by<br />

entering disable synchronization-switch, followed by enable<br />

synchronization-switch.<br />

● Wait 1 minute, then run status synchronization.<br />

● If Maintenance Name on the status screen shows “STRAT-3,” then the problem is<br />

resolved.<br />

If the Standby Tone-Clock circuit pack became active:<br />

● Check the connection between the Stratum-3 clock and the TN780 Tone-Clock circuit<br />

pack from which the system has just switched.<br />

● If there are no loose connections, then, replace the circuit pack containing the TN780<br />

Tone-Clock circuit pack.<br />

● Before switching back to the new TN780 Tone-Clock circuit pack, use test<br />

tone-clock location long to check that the Tone-Clock is receiving a signal from<br />

the Stratum-3 clock.<br />

● If every test passes, switch to the new Tone-Clock circuit pack using set tone-clock<br />

location override.<br />

● If Test #651 fails, then the original TN780 Tone-Clock circuit pack should be reinserted,<br />

and the cable between the Stratum-3 clock and the TN780 Tone-Clock circuit pack<br />

should be replaced.<br />

● If Test #651 continues to fail, then escalate the problem.<br />

● If slip alarms exist after following the repair procedures for any of the previous cases,<br />

clear the slip alarms by running test board clear. See Table 337: Timing Slip Error<br />

Types for a list of circuit packs and associated slip error log entries.<br />

● This error indicates that the Tone-Clock circuit pack in the master port network is not a<br />

TN780. If duplicate Tone-Clock circuit packs exist in the master port network, this error<br />

may mean that one or both Tone-Clock circuit packs are not TN780s. Verify that the<br />

Tone-Clock(s) in the master port network are TN780s.<br />

h. Error Type 1281: this Error Type corresponds to FAIL code 32 of the Stratum-3 Clock Alarm<br />

Query (#649): every clock unit failed.<br />

i. Error Type 1537: An OFF-BOARD alarm on the Stratum-3 clock, indicates a DS1 facility<br />

problem; an ON-BOARD alarm indicates a fault in either the Stratum-3 clock or the<br />

connection between the Stratum-3 clock and the switch. If the Stratum-3 clock cannot be<br />

referenced and the local oscillator on the TN780 Tone-Clock circuit pack must serve as the<br />

reference, a Major alarm is raised. Otherwise, a Minor alarm is raised.<br />

Communication Manager Release 5.0 Issue 4 January 2008 1249