Communication Manager Maintenance Object Repair Procedures<br />

Table 195: DS1C-BD Error Log Entries 2 of 2<br />

Error<br />

Type<br />

Aux<br />

Data<br />

Associated Test Alarm<br />

Level<br />

769 (q) 7 Failure Audit test<br />

(#949)<br />

1281(r) Failure Audit test<br />

(#949)<br />

1537 (s) Failure Audit test<br />

(#949)<br />

1793 (t) Failure Audit test<br />

(#949)<br />

2049 (u) Failure Audit test<br />

(#949)<br />

3329 (v) Failure Audit test<br />

(#949)<br />

On/Off<br />

Board<br />

Recommended Action<br />

MIN ON test board location<br />

MIN OFF test board location<br />

MAJ OFF test board location<br />

MAJ OFF test board location<br />

MAJ OFF test board location<br />

WRN OFF test board location<br />

Notes:<br />

When problems persist, resetting the DS1 converter circuit pack via reset board may<br />

temporarily resolve the error condition and restore service until further assistance is provided.<br />

a. Error Type 0: Run the short test sequence first. If every test passes, run the long test<br />

sequence. Refer to each test’s description, and follow its recommended procedures.<br />

b. Error Type 1: If the alarm is on board, then a major hardware error has occurred in a<br />

common part of the circuit pack, not circuit or packet specific. Replace the DS1 converter<br />

circuit pack.<br />

If the alarm is off board, then either a major hardware error has occurred in a common part<br />

of the circuit pack, or a good clock signal cannot be recovered from the synchronization<br />

source. The synchronization source can be the fiber link or any one of the DS1 facilities.<br />

1. Enter display errors and follow the associated repair procedures for any SYNC<br />

(Port Network Synchronization), TDM-CLK (TDM Bus Clock), and SNC-BD (Switch Node<br />

Clock Circuit Pack) errors.<br />

2. Enter display errors and follow the associated repair procedures for any FIBER-LK<br />

(Fiber Link) and DS1-FAC (DS1 Facility) errors.<br />

3. If the problem persists, replace the DS1 converter circuit pack.<br />

c. Error Type 18: the DS1 converter circuit pack has been busied out via busyout board.<br />

To resolve this error, release the DS1 converter circuit pack via the release board.<br />

764 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s<br />