Duplication Memory Board LEDs<br />

LED indicators of serial bus commands to the power supply<br />

Operation of the 655A power supply LED indicators for visual indication of serial bus commands<br />

to the power supply for power supply shutdown and ringing shutdown are described below.<br />

Power supply shutdown<br />

The 655A power supply can be commanded off for a period of time selectable from 1 to 255<br />

seconds. The intent is to allow a hard reset to the G650 chassis remotely. The yellow LED<br />

indicating correct operation of the 655A power supply is on for normal power supply operation.<br />

When the power supply is commanded off, the yellow LED blinks at a rate of 1 second on and<br />

100ms off, indicating that the power supply is operational but commanded off by the serial bus.<br />

Ringing shutdown<br />

The left hand power supply in the G650 cabinet is the master ringer. If the master ringer fails,<br />

ringing is transferred to the redundant power supply, if present. The red LED on the left hand<br />

power supply turns on and the yellow LED turns off, indicating failure of the power supply.<br />

The serial bus can command the ringer off for a period of 1 to 255 seconds. The purpose of this<br />

command is to verify redundant ringer operation through the serial bus remotely from the G650<br />

chassis. The red LED blinks at a rate of 1 second on and 100ms off, indicating that the power<br />

supply is operational but commanded off by the serial bus.<br />

A second command relating to ringer operation is the command to turn off the master ringer.<br />

This command shuts down the master ringer and transfers control to the redundant power<br />

supply. This command is used to permanently transfer ring voltage to the redundant power<br />

supply through the serial bus, in order to resolve a problem with the master ringer. The red LED<br />

blinks at a rate of 1 second on and 100ms off, indicating that the power supply is operational but<br />

commanded off by the serial bus.<br />

Duplication Memory Board LEDs<br />

WARNING: The<br />

! WARNING:<br />

DAJ1, DAL1, and DAJ2 Duplication Memory boards are not interchangeable.<br />

The DAJ1 only functions in the S8700 <strong>Server</strong>. The DAL1 functions in an S8710<br />

<strong>Server</strong> and an S8720 <strong>Server</strong> with standard configuration. The DAL2 functions in<br />

an S8720 <strong>Server</strong> running Communication Manager 4.0 or later with the extra<br />

large configuration.<br />

Communication Manager Release 5.0 Issue 4 January 2008 317