Communication Manager Maintenance Object Repair Procedures<br />

Table 509: BRI Port Local TDM Looparound Test (#619) 3 of 3<br />

Error<br />

Code<br />

2012<br />

2100<br />

2103<br />

1<br />

2<br />

7<br />

8<br />

Test<br />

Result<br />

Description / Recommendation<br />

ABORT Internal system error.<br />

Could not allocate the necessary resources to run this test.<br />

The system could not make the conference connection for the test.<br />

1. Retry the command at 1-minute intervals up to 5 times.<br />

2. If the test continues to abort, escalate the problem.<br />

FAIL 1 — TDM Looparound test failed on B1.<br />

2 — TDM Looparound test failed on B2.<br />

7 — Conference Circuit test failed on B1<br />

8 —- Conference Circuit test failed on B2.<br />

1. If the test fails repeatedly, try to reset the circuit pack if the other ports<br />

on the circuit pack are idle.<br />

2. If the test fails again, replace the circuit pack.<br />

PASS The BRI Port Local TDM Looparound test passed.<br />

Electronic Power Feed Restoral Test (#620)<br />

This test attempts to restore the Electronic Power Feed (EPF) on an ISDN-BRI port twice. In<br />

this test, the processor requests that the EPF be turned on for a given port. An attempt is made<br />

to turn on the power unit to the station or adjunct. If no current is being drawn by a station, this<br />

probably indicates that the station is not connected. No current being drawn by an adjunct is the<br />

normal condition. If an overcurrent condition is sensed (that is, too much current is being<br />

drawn), this condition may indicate a short in the wiring to the endpoint or adjunct. Depending<br />

on what condition is sensed, a message is returned stating that either the EPF was turned on<br />

successfully with no problems or that an overcurrent condition is sensed. This response is<br />

reported by the Electronic Power Feed Inquiry (#622), which follows in the testing sequence.<br />

EPF Restoral is attempted again by this test five seconds later. This test always passes for the<br />

TN2198 because it has no EPF. This test will always abort when run on the TN2208.<br />

1754 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s<br />