Communication Manager Maintenance Object Repair Procedures<br />

Table 412: Single-Carrier Cabinet Power Query Test (#79) 2 of 2<br />

Error<br />

Code<br />

Test<br />

Result<br />

Description / Recommendation<br />

1 FAIL There is a problem with the environment of the power system.<br />

1. The power supply to any one of the carriers may have been lost.<br />

a. Verify, and if necessary restore, AC power at the wall outlet for<br />

each carrier.<br />

b. Rerun the test. If the test still fails, proceed to step 2.<br />

2. One of the WP-91153 or 676-B power units for one of the carriers<br />

could be defective.<br />

a. If the yellow status LED on a WP-91153 or 676-B power unit is off,<br />

replace the power unit. See Chapter 11: Component replacement<br />

in Maintenance Procedures (03-300432).<br />

b. Rerun the test. If the test still fails, proceed with Step 3.<br />

3. The PN’s MAINT (Maintenance circuit pack) could be incorrectly<br />

reporting this error. Resolve every alarm on these MOs, and rerun the<br />

test. There are failures that can occur on the PN’s Maintenance circuit<br />

pack that will not be detected but that will cause many, if not all,<br />

environment tests to fail. If more than two environment tests are<br />

failing, replace the suspect circuit pack, depending on the system<br />

configuration, and rerun the test.<br />

4. If the test still fails, follow normal escalation procedures.<br />

PASS The PN’s Maintenance circuit pack has reported no problem with power.<br />

Tone Generator Crosstalk Test (#90)<br />

The Tone Generator Crosstalk Test verifies the ability of the Tone Generator to talk on a specific<br />

time slot. The other idle time slots are checked to make sure the Tone Generator put the tone on<br />

only the specified time slot.<br />

This test runs on the following maintenance objects:<br />

● TDM-CLK (TDM Bus Clock)<br />

● TONE-BD (Tone-Clock Circuit Pack)<br />

1544 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s<br />

2 of 2