Communication Manager Maintenance Object Repair Procedures<br />

Antithrashing and PNC Interchanges<br />

Following a spontaneous PNC interchange, subsequent PNC interchanges are prevented for 5<br />

minutes. This condition is indicated by y in the Interchange Disabled? field of the status<br />

pnc screen. After 5 minutes, the antithrashing timer expires, interchange decisions are<br />

re-enabled, and the field displays n.<br />

Note:<br />

Note: Should a catastrophic failure occur on the active PNC during the period when the<br />

Interchange Disabled? field is set to “yes,” there will be no spontaneous<br />

PNC interchange.<br />

Demand PNC interchanges also invoke anti-thrashing, but only for a period of 30 seconds.<br />

During antithrashing mode, demand interchanges are also prevented unless the override option<br />

is specified.<br />

CAUTION: Use<br />

! CAUTION:<br />

of this option may cause a service disruption.<br />

Repairs on the Standby PNC Components<br />

! CAUTION:<br />

CAUTION: If there is a TDM-CLK alarm, system timing may be routed through part of the<br />

standby PNC, and circuit switched data may be affected by the following repair<br />

procedures. This can happen, for example, when a slave tone/clock circuit pack<br />

experiences a loss of signal and switches to receive timing from the standby<br />

ATM-EI. In this case TDM-CLK 2305 error is logged, and the clock problem<br />

should be addressed first, if possible.<br />

To repair PNC components in a duplicated PNC proceed as follows:<br />

1. Most repairs involve fixing a single fault on the standby PNC. Enter set pnc lock or<br />

busy-out pnc to prevent an interchange into the PNC being repaired.<br />

2. If a faulty component exists on the active PNC, this also means that the standby PNC is<br />

more severely faulted. Normally, the standby PNC is repaired first, since it is the most<br />

severely impaired.<br />

To repair the active PNC (the standby is already repaired), enter set pnc unlock, which<br />

generates a spontaneous interchange. In a PNC demand interchange with reset pnc<br />

interchange use the override-and-lock qualifier for the active PNC. The<br />

override-and-lock option ensures that no subsequent interchange can occur during<br />

the repair of the standby PNC. A demand interchange may not be necessary if the following<br />

conditions drive a spontaneous interchange:<br />

● The anti-thrashing period from the last interchange has expired.<br />

542 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s