Communication Manager Maintenance Object Repair Procedures<br />

Table 425: Cabinet Temperature Query Test (#122) 4 of 6<br />

Error<br />

Code<br />

Test<br />

Result<br />

1 FAIL<br />

(cont’d)<br />

Description / Recommendation<br />

NONVARIABLE-SPEEDFAN ASSEMBLIES in older or upgraded<br />

cabinets: The AHD1 circuit pack has reported an air-flow problem. The<br />

temperature difference between the air intake and the air exhaust is at<br />

least 150C (590F)) and the absolute temperature at the top of the cabinet<br />

is at least 50 0 C (122 0 F). The fans should be running at high speed. If<br />

none of the fans are running:<br />

1. Look for an resolve every alarm against CARR-POW (Carrier Power<br />

Supply).<br />

S8700-series IP-PNC Look for an resolve every alarm against<br />

RMC-ENV (Power/Fan Sensors).<br />

2. Verify that 48 VDC is available to the fan wiring harness connector<br />

between pin pairs 2/3, 8/9, and 10/11. The tolerable range for this<br />

measurement is -42.5 V to -52.5 V.<br />

If 48 VDC is present and the fans are not running, replace the AHD1<br />

circuit pack. If the fans still do not run, escalate the problem.<br />

3. If 48 VDC is absent, replace the CFY1B current limiter card.<br />

If the fans still do not run, escalate the problem.<br />

If some fans are running and some not, replace the defective fans.<br />

4. If every fan can be started, wait 5 minutes and rerun the test. If the<br />

test fails again, proceed to the next step.<br />

5. If every fan is running but not at high speed, measure the cabinet<br />

temperature at the air intake and the air exhaust at the top of the<br />

cabinet.<br />

a. If the 15 0- /50 0- C criteria is met, there is a problem with the AHD1<br />

circuit pack or the fans. Replace the AHD1 circuit pack and/or<br />

fans. If the fans run at high speed, wait 5 minutes for the cabinet to<br />

cool, then retest. If the test fails, escalate the problem.<br />

b. If the 15 0- /50 0- C criteria is not met, environmental maintenance is<br />

incorrectly reporting this condition. Resolve every error<br />

(S8700-series Fiber-PNC: MAINT (PN Maintenance Circuit Pack))<br />

and retest. If the test fails, escalate the problem.<br />