Communication Manager Maintenance Object Repair Procedures<br />

Table 379: Battery and Power Supply Query Test (#5) 6 of 7<br />

Error<br />

Code<br />

8<br />

(cont’d)<br />

Test<br />

Result<br />

FAIL<br />

(cont’d)<br />

Description / Recommendation<br />

d. If there is an alarm and every LED is OK (PWR OK and<br />

BOK) on the rectifier modules and the BIU (Battery Interface<br />

Unit), verify that the BIU and the RM0850 rectifiers are<br />

seated properly (plugged in). If the BOK LED on the BIU is<br />

OK, check the number of rectifiers serving this cabinet:<br />

No. of carriers/cabinet No. of rectifiers/cabinet<br />

1 2<br />

2 3<br />

3 3<br />

4 4<br />

5 4<br />

If the number of rectifiers is correct replace the maintenance<br />

circuit pack in the PN.<br />

10 FAIL DC-powered cabinet: The PN’s Maintenance circuit pack is<br />

incorrectly reporting a problem with power. Replace the suspect circuit<br />

pack and run the test again.<br />

AC-powered cabinet: Error codes 2 and 8 have occurred. Refer to<br />

these descriptions. Also, refer to this test’s description for Error Code<br />

14.<br />

12 FAIL DC-powered cabinet: The PN’s Maintenance circuit pack is<br />

incorrectly reporting a problem with power. Replace the suspect circuit<br />

pack and run the test again.<br />

AC-powered cabinet: Error codes 4 and 8 have occurred. Refer to<br />

these descriptions. Also, refer to this test’s description for Error Code<br />

14.<br />

14 FAIL DC-powered cabinet: The PN’s Maintenance circuit pack is<br />

incorrectly reporting a problem with power. Replace the suspect circuit<br />

pack and run the test again.<br />

AC-powered cabinet: Error codes 2, 4, and 8 have occurred. Refer to<br />

these descriptions.<br />

This could also indicate that the detection logic on the PN’s MAINT<br />

(Maintenance) circuit pack is defective. Such an error will not be<br />

detected by the respective maintenance. If many environment tests are<br />

failing, replace the suspect circuit pack, depending on the system<br />

configuration.<br />

1440 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s<br />

6 of 7