Table 163: CAB-TEMP Error Log Entries 2 of 2<br />

Error<br />

Type<br />

Aux<br />

Data<br />

Associated Test Alarm<br />

Level<br />

CAB-TEMP (Cabinet Temperature)<br />

513 (c) Power supply<br />

temperature test (#1538) MIN ON test enviroment location<br />

MAJ 1<br />

test board location<br />

769 (d) Power supply fan test<br />

(#1538)<br />

On/Off<br />

Board<br />

Notes<br />

a. Error Type 1: the inlet temperature is over the threshold—120 o Fahrenheit (49 o Celsius).<br />

Run test board and check the results of the Power Supply Temperature Test (#1537).<br />

b. Error Type 257: the exhaust temperature is over the threshold—120 o Fahrenheit (49 o<br />

Celsius). Run test board and check the results of the Power Supply Temperature Test<br />

(#1537).<br />

c. Error Type 513: the hot spot temperature is over the threshold. Run test board and<br />

check the results of the Power Supply Temperature Test (#1537).<br />

d. Error Type 769: the fan alarm is active. Run test board and check results of the Power<br />

Supply Temperature Test (#1537).<br />

Demand test descriptions and error codes<br />

MIN ON test enviroment location<br />

test board location<br />

1. This is a minor alarm if there is a redundant power supply, and a major alarm if there is only one power<br />

supply.<br />

Investigate tests in the order presented. By clearing errors associated with the first test, errors<br />

generated from other tests may also be cleared. Click on the link to see the full description of<br />

the test, error codes, and recommended actions.<br />

Order of investigation Short test<br />

sequence<br />

Recommended Action<br />

Long test<br />

sequence<br />

D/ND<br />

Power Supply Temperature Test (#1537) X X Nondestructive<br />

Power Supply Fan Test (#1538) X X Nondestructive<br />

2 of 2<br />

Communication Manager Release 5.0 Issue 4 January 2008 619