Table 554: Packet Interface Private Looparound Test (#885) 2 of 3<br />

Error<br />

Code<br />

Packet Interface Private Looparound Test (#885)<br />

1335 ABORT Internal IPSI error. The Packet Interface module is on the standby IPSI,<br />

so this test is not allowed to run.<br />

1. Enter set ipserver-interface location to make the<br />

standby Packet Interface active.<br />

2. Rerun the test.<br />

2000 ABORT Response to the test was not received within the allowed time.<br />

1. Retry the command at 1-minute intervals up to 3 times.<br />

2500 ABORT Internal system error<br />

1. Retry the command at 1-minute intervals up to 3 times.<br />

1<br />

2<br />

3<br />

Test<br />

Result<br />

Description / Recommendation<br />

FAIL The Private Link Broadcast Looparound Test failed.<br />

The Private Level-2 Looparound Test failed.<br />

The Private Level-3 Looparound Test failed.<br />

1. The Packet Interface module on the IPSI circuit pack enters a<br />

fatal-fault state when this error occurs, and the Packet Interface is<br />

put in a out-of-service state. By the time action is taken, the test<br />

should abort with ABORT code 1137, and a demand reset should be<br />

used to test the Packet Interface.<br />

2. This may be the result of old firmware not supporting new software<br />

operation. Verify the IPSI circuit pack’s firmware vintage and<br />

download the new firmware if appropriate.<br />

3. The firmware image on the IPSI circuit pack may have been<br />

corrupted. Download the appropriate firmware image.<br />

4. Retry the command.<br />

5. If the same Error Code occurs, enter reset packet-interface<br />

location to reset the Packet Interface. See the repair procedures<br />

for Packet Interface Reset Test (#889).<br />

6. If the test continues to fail, replace the IPSI circuit pack.<br />

2 of 3<br />

Communication Manager Release 5.0 Issue 4 January 2008 1877