Cabinet Temperature Query Test (#122)<br />

Cabinet Temperature Query Test (#122)<br />

This test queries for the status of the temperature and fan sensors in the cabinet. This test is run<br />

on the following maintenance objects:<br />

● AC-POWER<br />

● CABINET (Cabinet Sensors)<br />

● CARR-POW (Carrier Power Supply)<br />

● EMG-XFER (Emergency Transfer)<br />

● POWER<br />

Table 425: Cabinet Temperature Query Test (#122) 1 of 6<br />

Error<br />

Code<br />

Test<br />

Result<br />

Description / Recommendation<br />

1000 ABORT System resources required to run test are not available.<br />

1. Retry the command at 1-minute intervals up to 5 times.<br />

2000 ABORT Response from the test was not received within the time allowed.<br />

1. Retry the command at 1-minute intervals up to 5 times.<br />

2. S8700-series: If the test continues to abort with Error Code 2000, check<br />

for power problems with the PN’s A carrier.<br />

2029<br />

2319<br />

2500<br />

S8700-series Fiber-PNC: Look for and resolve every AC-POWER and<br />

CARR-POW (Carrier Power Supply) alarm in a multicarrier cabinet or<br />

DC-POWER (Single-Carrier Cabinet Environment) alarm in a<br />

single-carrier cabinet. Repeat the test. If the test continues to abort<br />

with error code 2000, check for and resolve every MAINT (PN<br />

Maintenance Circuit Pack) error in a PN. Repeat the test.<br />

S8700-series IP-PNC:Look for and resolve every RMC-ENV (Power/Fan<br />

Sensors) alarm. Repeat the test.<br />

ABORT Internal system error<br />

1. Retry the command at 1-minute intervals up to 5 times.<br />

1 of 6<br />

Communication Manager Release 5.0 Issue 4 January 2008 1573