Communication Manager Maintenance Object Repair Procedures<br />

The following is an example for running a long test sequence twice on a port on a circuit pack:<br />

test port UUCSSpp l r 2<br />

● UU = the universal cabinet number (1 - 64)<br />

● C = the carrier designation (A, B, C, D, or E)<br />

● SS = the circuit pack slot number (01, 02,...)<br />

● pp = the 2-digit port number (01, 02,...)<br />

● l = long test sequence<br />

● r = repeat<br />

● 2 = the number of times the test sequence should be repeated.<br />

The following is an example for testing a port on a media module. It runs the short test<br />

sequence:<br />

test port GGGVSpp r 3<br />

● GGG = the media gateway number (1 - 250)<br />

● V = the literal letter V, which designates a media gateway<br />

● S = the media module number (1 - 9)<br />

● pp = the 2-digit port number (01, 02,...)<br />

● r = repeat<br />

Alarm levels<br />

● 3 = the number of times the test sequence should be repeated<br />

During normal operations, software or firmware may detect error conditions concerning specific<br />

Maintenance Objects (MOs). The system automatically attempts to fix or circumvent the<br />

problem. The alarms are classified depending on their effect on system operation:<br />

● Major alarms — Failures that cause critical degradation of service. These alarms require<br />

immediate attention.<br />

● Minor alarms — Failures that cause some degradation of service, but do not render a<br />

crucial portion of the system inoperable. A minor alarm typically affects a few trunks or<br />

stations or a single feature. Minor alarms require attention, but the consequences are not<br />

immediate.<br />

● Warning alarms — Failures that cause no significant degradation of service or failures in<br />

equipment. These failures are not reported to INADS or the attendant console.<br />

● On-Board problems originate in the circuitry on the alarmed Media Module or circuit pack.<br />

416 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s