Communication Manager Maintenance Object Repair Procedures<br />

Nominal Power Holdover<br />

Multicarrier Cabinets<br />

Two types of battery holdover are available:<br />

● The small battery assembly provides short-term battery holdover. If AC power fails, 48<br />

VDC batteries power the system for:<br />

- 15 seconds in a PN cabinet<br />

- 10 minutes in the expansion control carrier in the “A” position of a PN cabinet<br />

● Some AC-powered multicarrier cabinets (MCCs) contain three 48-Volt batteries and a<br />

battery charger (397C) to provide backup power in case power is interrupted. The<br />

holdover times are identical to those above.<br />

Single-Carrier Cabinets<br />

A holdover circuit in the power supply allows a system to operate normally during AC power<br />

interruptions. When AC input power fails, reserve batteries supply power to the memory and<br />

processor circuit packs and fans for two minutes. Every port circuit pack is inactive during this<br />

time. The power supply contains a battery charger to charge the holdover batteries.<br />

Error log entries and recommended actions<br />

Table 104: AC-POWER Error Log Entries<br />

Error<br />

Type<br />

0 1<br />

Aux<br />

Data<br />

Associated Test Alarm<br />

Level<br />

On/Off<br />

Board<br />

Demand test descriptions and error codes<br />

Recommended action<br />

0 Any Any Any test environment location<br />

513 Any AC Power Query<br />

Test (#78)<br />

WRN OFF test environment location<br />

1. Run the short test sequence first. If every test passes, run the long test sequence. Refer to each<br />

appropriate test’s description, and follow its recommended procedures.<br />

Investigate tests in the order presented. By clearing errors associated with the first test, errors<br />

generated from other tests may also be cleared. Click on the link to see the full description of<br />

the test, error codes, and recommended actions.<br />

422 Maintenance <strong>Alarms</strong> for <strong>Avaya</strong> Communication Manager, Media Gateways and <strong>Server</strong>s