Table 638: Power Supply Recycle Test (#1534) 2 of 3<br />

Error<br />

Code<br />

Test<br />

Result<br />

Description and recommendation<br />

Power Supply Recycle Test (#1534)<br />

1977 ABORT There is an active Expansion ArchAngel (EAA) in the carrier that a<br />

recycle was attempted on. Recycling the carrier with the active EAA will<br />

result in loss of network control to the entire port network.<br />

1. If the TN2312 IPSI circuit packs are duplicated, move network<br />

control to the other carrier (IPSI) using the following commands:<br />

● list ipserver-interface to verify that the IPSI in the<br />

carrier of interest is active.<br />

● set ipserver cabinet a or b to move the control to the<br />

other IPSI.<br />

● recycle carrier cabinet a or b to recycle the carrier.<br />

2. If the TN2312 IPSI circuit packs are not duplicated.<br />

● Enter recycle carrier override to recycle the carrier.<br />

1980 ABORT The power supply is in a carrier with an active expansion interface (EI).<br />

1. Enter status port-network nn to verify that the EI (A or B) in<br />

the carrier of interest is active.<br />

2. Enter reset pnc interchange to move port network<br />

connectivity to the other expansion interface.<br />

3. Enter recycle carrier<br />

1987 ABORT The power supply data was not valid.<br />

1. Repeat the command at one-minute intervals 1 to 3 times.<br />

2000 ABORT The response to a query was not received in the time allowed.<br />

1. Repeat the command at one-minute intervals 1 to 3 times.<br />

2029 ABORT There is a problem communicating with the environmental maintenance<br />

firmware.<br />

1. Run test maintenance nn<br />

2100 ABORT The system could not allocate resources.<br />

1. Repeat the command at one-minute intervals 1 to 3 times.<br />

2. Escalate the problem if the test continues to abort.<br />

2319 ABORT The EPN is out of range.<br />

2 of 3<br />

Communication Manager Release 5.0 Issue 4 January 2008 2041