Table 284: Battery <strong>and</strong> Power Supply Query Test (#5) 3 of 7<br />

Error<br />

Code<br />

2029<br />

2319<br />

2320<br />

2500<br />

Test<br />

Result<br />

Description / Recommendation<br />

Battery <strong>and</strong> Power Supply Query Test (#5)<br />

ABORT Internal system <strong>error</strong><br />

1. Retry the comm<strong>and</strong> at 1-minute intervals up to 5 times.<br />

2 FAIL DC-powered cabinet: The PN’s Maintenance circuit pack is<br />

incorrectly reporting a problem with power. Replace the suspect circuit<br />

pack <strong>and</strong> run the <strong>test</strong> again.<br />

AC-powered cabinet: The system is in nominal power holdover, <strong>and</strong><br />

the battery is so low that the system will disconnect power very shortly.<br />

1. If power returns, the port carriers in the PN should power-up<br />

again. Every circuit pack should be reinserted, <strong>and</strong> the system<br />

should continue to operate normally. There will probably be a<br />

minor alarm against battery <strong>and</strong> battery charger due to the fact<br />

that the batteries are recharging.<br />

2. If power does not return, the system will shut down to prevent<br />

damage to the batteries. Restore power, <strong>and</strong> the system will<br />

reboot. No manual intervention is required.<br />

3. Rerun the <strong>test</strong>. If the <strong>test</strong> still fails, the PN’s MAINT (Maintenance)<br />

circuit pack could be reporting this condition incorrectly. Resolve<br />

every alarm on this MO, <strong>and</strong> rerun the <strong>test</strong>. There are failures that<br />

can occur on the PN’s Maintenance circuit pack that will not be<br />

detected by their respective maintenance, but which will cause<br />

many, if not every, environment <strong>test</strong>s to fail. If many environment<br />

<strong>test</strong>s are failing, the suspect circuit pack, depending on the<br />

system configuration, should be replaced <strong>and</strong> the <strong>test</strong> rerun.<br />

3 of 7<br />