d. Error Type 25: The 24/32-chel option switch setting on the TN1654 circuit pack does not<br />

match the administered Bit Rate on the fiber-link screen. If the on-board switch setting is<br />

wrong, the circuit pack must be physically removed to change the setting of the board<br />

option switch. If the administered bit rate is wrong, use change fiber-link to correct it.<br />

e. Error Type 218: The DS1 converter board is physically installed in a slot different than its<br />

administered slot. Remove the DS1 converter board <strong>and</strong> install it in its administered slot or<br />

execute remove fiber-link followed by add fiber-link to re-add the fiber-link<br />

setting the DS1 converter board’s administered location to the physically installed slot.<br />

f. Error Type 257: A minor hardware <strong>error</strong> has occurred in a common part of the circuit pack,<br />

not circuit or packet specific. Replace the DS1 converter circuit pack.<br />

g. Error Type 513, Aux Data 1: A major hardware problem has occurred that affects only<br />

circuit data being received from the DS1 converter circuit pack. Replace the DS1 converter<br />

circuit pack.<br />

h. Error Type 513, Aux Data 2: A major hardware problem has occurred that affects only<br />

circuit data being transmitted from the DS1 converter circuit pack. Replace the DS1<br />

converter circuit pack.<br />

i. Error Type 513, Aux Data 3: A major hardware problem has occurred that affects only<br />

packet data being received from the DS1 converter circuit pack. Replace the DS1 converter<br />

circuit pack.<br />

j. Error Type 513, Aux Data 4: A major hardware problem has occurred that affects only<br />

packet data being transmitted from the DS1 converter circuit pack. Replace the DS1<br />

converter circuit pack.<br />

k. Error Type 513, Aux Data 5: A major lightwave transceiver transmit <strong>error</strong> occurred that<br />

affects data transmitted from the fiber link to the DS1 facility. Replace the DS1 converter<br />

circuit pack.<br />

l. Error Type 769, Aux Data 1: This <strong>error</strong> only applies to TN574 DS1 converter circuit packs.<br />

If the alarm is on board, then a minor hardware problem has occurred that affects only<br />

circuit data being received from the DS1 converter circuit pack. Replace the DS1 converter<br />

circuit pack.<br />

If the alarm is off board, then either a minor hardware problem has occurred that affects<br />

only circuit data being received into the DS1 converter circuit pack or a good clock signal<br />

cot be recovered from one of the DS1 facilities.<br />

1. Enter display <strong>error</strong>s <strong>and</strong> follow the associated repair procedures for any SYNC<br />

(Port Network Synchronization), TDM-CLK (TDM Bus Clock), <strong>and</strong> SNC-BD (Switch<br />

Node Clock Circuit Pack) <strong>error</strong>s.<br />

2. Enter display <strong>error</strong>s <strong>and</strong> follow the associated repair procedures for any<br />

DS1-FAC (DS1 Facility) <strong>error</strong>s.<br />

3. If the problem persists, replace the DS1 converter circuit pack.<br />

392 Maintenance Alarms for Communication Manager, Media Gateways <strong>and</strong> Servers