Error log entries <strong>and</strong> recommended actions<br />

Table 213: POWER Error Log Entries<br />

Error<br />

Type<br />

Aux<br />

Data<br />

Associated Test Alarm<br />

Level<br />

Notes:<br />

a. Error Type 0: run the short <strong>test</strong> sequence first. If every <strong>test</strong> passes, run the long <strong>test</strong><br />

sequence. Refer to each <strong>test</strong>’s description, <strong>and</strong> follow its procedures.<br />

b. Error Type 3840: this <strong>error</strong> is valid only for AC-powered multicarrier cabinets with battery<br />

backup. For DC-powered cabinets, ignore the <strong>error</strong>; it cannot be cleared.<br />

For AC-powered cabinets, see if the battery charger is connected. If the cabinet is powered<br />

by a UPS, there is no battery backup <strong>and</strong> this <strong>error</strong> can be ignored.<br />

<strong>Dem<strong>and</strong></strong> <strong>test</strong> <strong>descriptions</strong> <strong>and</strong> <strong>error</strong> <strong>codes</strong><br />

On/Off<br />

Board<br />

Investigate <strong>test</strong>s in the order presented. By clearing <strong>error</strong>s associated with the first <strong>test</strong>, <strong>error</strong>s<br />

generated from other <strong>test</strong>s may also be cleared. Click on the link to see the full description of<br />

the <strong>test</strong>, <strong>error</strong> <strong>codes</strong>, <strong>and</strong> recommended actions.<br />

776 Maintenance Alarms for Communication Manager, Media Gateways <strong>and</strong> Servers<br />

Recommended Action<br />

0 (a) 0 Any Any Any <strong>test</strong> environment UU<br />

1 Any Battery <strong>and</strong> Power Supply<br />

Query (#5) (Error Code 8)<br />

MIN ON <strong>test</strong> environment UU<br />

257 Any Battery <strong>and</strong> Power Supply<br />

Query (#5) (Error Code 4)<br />

MIN ON <strong>test</strong> environment UU<br />

769 Any Battery <strong>and</strong> Power Supply<br />

Query (#5) (Error Code 2)<br />

MIN ON <strong>test</strong> environment UU<br />

3840 (b) 1005<br />

1028<br />

Battery <strong>and</strong> Power Supply<br />

Query (#5)<br />

Order of Investigation Short Test<br />

Sequence<br />

<strong>test</strong> environment UU<br />

Long Test<br />

Sequence<br />

D/ND 1<br />

Battery <strong>and</strong> Power Supply Query Test (#5) X X ND<br />

AC Power Query Test (#78) X X ND<br />

OLS/Power Unit Query Test (#127) (Carrier E) X X ND<br />

OLS/Power Unit Query Test (#127) (Carrier D) X X ND<br />