Maintenance <strong>Dem<strong>and</strong></strong> Tests<br />

Table 326: OLS Recycle Test (#116) 2 of 2<br />

Error<br />

Code<br />

255 FAIL Did not receive uplink alarm from the carrier.<br />

1. Retry the comm<strong>and</strong> at 1-minute intervals up to 5 times.<br />

1 (E)<br />

2 (D)<br />

4 (A)<br />

8 (B)<br />

16 (C)<br />

Test<br />

Result<br />

Description / Recommendation<br />

FAIL There is a problem with one or both OLSs on the cycled carrier.<br />

1. Since the OLS Recycle <strong>test</strong> failed, both OLSs in the cycled carrier<br />

should have been powered off by the system software. Both OLSs<br />

should have a red status LED turned on instead of amber. Since<br />

the OLS Query <strong>test</strong> is a subset of the OLS Recycle <strong>test</strong>, the OLS<br />

Query <strong>test</strong> (#127) should also fail. Run the OLS Query <strong>test</strong> by<br />

using<br />

<strong>test</strong> environment location where location is the<br />

appropriate cabinet number.<br />

2. If Test #127 fails, follow the repair procedures for the OLS/Power<br />

Unit Query Test (#127).<br />

PASS Both OLSs in the recycled carrier were found to be healthy by a PN’s<br />

Maintenance circuit pack after the OLSs were powered down <strong>and</strong> back<br />

up. If the status LEDs on both OLSs are not showing amber, then the<br />

MAINT (Maintenance) circuit pack may have incorrectly reported the<br />

state of the OLSs. Resolve any alarms on these MOs.<br />

Ring Generator Initialization Test (#117)<br />

The Ring Generator Initialization Test sends a request to the active TN768, TN780, TN2182<br />

Tone-Clock or TN2312AP/BP IPSI circuit pack’s Tone-Clock circuit to monitor the voltage. The<br />

Tone-Clock responds with an <strong>error</strong> if the ringing voltage falls too low.<br />

This <strong>test</strong> is run on the following maintenance objects:<br />

● AC-POWER<br />

● CABINET (Cabinet Sensors)<br />

● CARR-POW (Carrier Power Supply)<br />

● DC-POWER (Single-Carrier Cabinet Environment)<br />

● EMG-XFER (Emergency Transfer)<br />

● EXT-DEV (External Device Alarm)<br />

1208 Maintenance Alarms for Communication Manager, Media Gateways <strong>and</strong> Servers<br />