CAB-TEMP (Cabinet Temperature)<br />

G650<br />

CAB-TEMP monitors the G650 <strong>and</strong> the 655A for the following:<br />

● The power supply<br />

- Inlet temperature<br />

- Hot spot temperature status<br />

- Fan speed<br />

- Fan alarm lead<br />

CAB-TEMP (Cabinet Temperature)<br />

● The G650 carrier exhaust temperature<br />

The serial bus is used by the TN2312BP IPSI to obtain this information from each power supply<br />

in a G650 media gateway. There is only one outlet temperature sensor <strong>and</strong> fan assembly in a<br />

G650, so information obtained from dual power supplies (slot 0 <strong>and</strong> 15) is redundant.<br />

Refer to Figure 66: G650 Cabinet Environmental Hardware Components for further<br />

information.<br />

Note: Fan/filter<br />

MO Name in Log Alarm Level Initial Comm<strong>and</strong> to Run Full name of MO<br />

CAB-TEMP MAJ<br />

MIN<br />

Note:<br />

replacement procedures for the CMC1 <strong>and</strong> G600 media gateways are<br />

to be found under Variable-speed fans in Maintenance Procedures for <strong>Avaya</strong><br />

Aura Communication Manager, Media Gateways <strong>and</strong> Servers (03-300432).<br />

Error log entries <strong>and</strong> recommended actions<br />

Table 67: CAB-TEMP Error Log Entries 1 of 2<br />

Error<br />

Type<br />

Aux<br />

Data<br />

Associated Test Alarm<br />

Level<br />

1 (a) Power supply<br />

temperature <strong>test</strong> (#1537)<br />

257 (b) Power supply<br />

temperature <strong>test</strong> (#1537)<br />

<strong>test</strong> board location Cabinet Temperature<br />

On/Off<br />

Board<br />

Recommended Action<br />

MIN OFF <strong>test</strong> enviroment location<br />

<strong>test</strong> board location<br />

MIN ON <strong>test</strong> enviroment location<br />

<strong>test</strong> board location<br />

1 of 2<br />

Issue 5 May 2009 243