Table 330: Cabinet Temperature Query Test (#122) 4 of 6<br />

Error<br />

Code<br />

Test<br />

Result<br />

1 FAIL<br />

(cont’d)<br />

Description / Recommendation<br />

Cabinet Temperature Query Test (#122)<br />

NONVARIABLE-SPEEDFAN ASSEMBLIES in older or upgraded<br />

cabinets: The AHD1 circuit pack has reported an air-flow problem. The<br />

temperature difference between the air intake <strong>and</strong> the air exhaust is at<br />

least 15 0 C (59 0 F)) <strong>and</strong> the absolute temperature at the top of the cabinet<br />

is at least 500C (1220F). The fans should be running at high speed. If<br />

none of the fans are running:<br />

1. Look for an resolve every alarm against CARR-POW (Carrier Power<br />

Supply).<br />

S8700-series IP-PNC Look for an resolve every alarm against<br />

RMC-ENV (Power/Fan Sensors).<br />

2. Verify that 48 VDC is available to the fan wiring harness connector<br />

between pin pairs 2/3, 8/9, <strong>and</strong> 10/11. The tolerable range for this<br />

measurement is -42.5 V to -52.5 V.<br />

If 48 VDC is present <strong>and</strong> the fans are not running, replace the AHD1<br />

circuit pack. If the fans still do not run, escalate the problem.<br />

3. If 48 VDC is absent, replace the CFY1B current limiter card.<br />

If the fans still do not run, escalate the problem.<br />

If some fans are running <strong>and</strong> some not, replace the defective fans.<br />

4. If every fan can be started, wait 5 minutes <strong>and</strong> rerun the <strong>test</strong>. If the<br />

<strong>test</strong> fails again, proceed to the next step.<br />

5. If every fan is running but not at high speed, measure the cabinet<br />

temperature at the air intake <strong>and</strong> the air exhaust at the top of the<br />

cabinet.<br />

a. If the 150- /500-C criteria is met, there is a problem with the<br />

AHD1 circuit pack or the fans. Replace the AHD1 circuit pack<br />

<strong>and</strong>/or fans. If the fans run at high speed, wait 5 minutes for the<br />

cabinet to cool, then re<strong>test</strong>. If the <strong>test</strong> fails, escalate the<br />

problem.<br />

b. If the 15 0- /50 0- C criteria is not met, environmental maintenance<br />

is incorrectly reporting this condition. Resolve every <strong>error</strong><br />

(S8700-series Fiber-PNC: MAINT (PN Maintenance Circuit Pack))<br />

<strong>and</strong> re<strong>test</strong>. If the <strong>test</strong> fails, escalate the problem.<br />

4 of 6<br />

Issue 5 May 2009 1219