TDM-CLK (TDM Bus Clock)<br />

e. Error Type 257: the Tone-Clock circuit pack in PN 1 is not a TN780 although Stratum-3<br />

synchronization is administered. Either:<br />

1. If a Stratum-3 clock is being used, replace this Tone-Clock with a TN780.<br />

2. If not, change synchronization administration to Stratum 4.<br />

f. Error Type 513: the tone-clock has reported an out-of-lock condition. A aux value of 1<br />

indicates this <strong>error</strong> is an out-of-lock with the primary reference. An Aux Data value of 2<br />

indicates that this <strong>error</strong> is an out-of-lock with the secondary reference. It could not lock onto<br />

the frequency of that synchronization reference. This will lead to a change in the<br />

synchronization reference if the condition continues.<br />

S8700 series | S8500<br />

g. Error Type 769: The IPSI’s Tone-Clock circuit or Tone-Clock circuit pack might be defective,<br />

however it may be a software failure that can be corrected by <strong>test</strong>ing.<br />

1. Check to see if the board is duplicated (list cabinet <strong>and</strong> status<br />

port-network) on the affected port network.<br />

2. If the board is not duplicated, use <strong>test</strong> tone-clock location long to resolve<br />

the <strong>error</strong>s. The long <strong>test</strong> resets the board <strong>and</strong> is required to reload on-board RAM<br />

associated with the TN2182’s DSPs. The effect is that tone detectors are taken out of<br />

service momentarily <strong>and</strong> tones are removed from the TDM bus for about 10 seconds,<br />

meaning that no dial tone or touch tones are available during this interval. This will<br />

probably not affect calls in progress, but could cause a call origination to abort or a<br />

user not to get dial tone when going off-hook.<br />

3. If every <strong>test</strong> passes <strong>and</strong> the alarm does not resolve, re<strong>test</strong> with <strong>test</strong> tone-clock<br />

location long clear.<br />

4. If the <strong>test</strong> passes, terminate the repair process. If the <strong>test</strong> fails, replace the circuit pack<br />

at the customer’s convenience.<br />

5. If this <strong>error</strong> was logged against the st<strong>and</strong>by Tone-Clock, <strong>and</strong> if the Aux Data value was<br />

18369, SYNC (Synchronization) maintenance acts on this <strong>error</strong>. No corrective action is<br />

required. For any other Aux Data, go to the next step.<br />

6. If the board is duplicated, switch to the st<strong>and</strong>by side (set tone-clock).<br />

7. Test the alarmed board (<strong>test</strong> tone-clock location long). This resets the<br />

board <strong>and</strong> is required to reload on-board RAM associated with the TN2182’s DSPs.<br />

8. If every <strong>test</strong> passes <strong>and</strong> the alarm does not resolve, re<strong>test</strong> (<strong>test</strong> tone-clock<br />

location long clear).<br />

9. If the <strong>test</strong> passes, terminate the repair process. If the <strong>test</strong> fails, replace the circuit pack<br />

at the customer’s convenience.<br />

Issue 5 May 2009 967