Maintenance <strong>Dem<strong>and</strong></strong> Tests<br />

Table 376: Expansion Interface 2-Way Transmission Test (#241) 4 of 7<br />

Error<br />

Code<br />

Test<br />

Result<br />

Description / Recommendation<br />

1394 ABORT The EI circuit pack is out of service <strong>and</strong> the <strong>test</strong> cot be run. This<br />

condition is due to a change in the EI circuit pack’s ability to<br />

communicate with the EI or SNI circuit pack on the other end of the fiber.<br />

1. Run Test #237, <strong>and</strong> check the Error Log for EXP-INTF Error Type<br />

1281. If Error Type 1281 is present or if Test #237 foes not pass,<br />

see repair procedures for Test #237, in Table 373: Expansion<br />

Interface Neighbor Query Test (#237)<br />

1395 ABORT This <strong>test</strong> cot run on an EI circuit pack if it is part of the B-side PNC <strong>and</strong><br />

Duplicated PNC is not enabled.<br />

1. If this <strong>test</strong> needs to run on this EI circuit pack, enable PNC with the<br />

change system-parameters duplication comm<strong>and</strong>.<br />

2. Prevent the system from doing a PNC interchange by entering<br />

set pnc lock.<br />

3. Repeat this <strong>test</strong>.<br />

1413 ABORT This <strong>test</strong> requires the use of a Tone-Clock circuit in each of the PNs<br />

used in this <strong>test</strong>. A Tone-Clock circuit is absent from one of the PNs.<br />

1. Verify that there is an IPSI or Tone-Clock circuit pack in the same<br />

PN as the Expansion Interface circuit pack under <strong>test</strong>.<br />

2. In a Direct Connect configuration, verify that there is a Tone-Clock<br />

circuit pack in the PN where the neighbor EI circuit pack resides.<br />

3. In a Center Stage Switch configuration, verify that there is at least<br />

one other PN, besides the PN where the EI circuit pack under <strong>test</strong><br />

resides, with a Tone-Clock circuit pack.<br />

1414 ABORT The active Tone-Clock circuit in one of the PNs being used for the <strong>test</strong><br />

has a MAJOR or MINOR alarm logged against it.<br />

1. Enter display alarms <strong>and</strong> resolve any TONE-BD (Tone-Clock<br />

Circuit Pack) <strong>and</strong> TONE-PT (Tone Generator) alarms.<br />

1956 ABORT ACL to the board is not up. Check the ACL status with list sys-link<br />

<strong>and</strong> follow the repair procedures for SYS-LINK (System Links).<br />

1318 Maintenance Alarms for Communication Manager, Media Gateways <strong>and</strong> Servers<br />